22 Lý Tự Trọng, Minh Khai, Hồng Bàng, Hải Phòng.
itvc.haiphong@itvc-global.com
Chi tiết sản phẩm
Measurement of short circuit loop impedance (ZL-PE, ZL-N, ZL-L)
Measuring range according to IEC61557: 0,13…1999? for 1,2m test leads; 0,25…1999? for UNI-SCHUKO adapter
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(5% m.v. + 3 Digits) |
20,0...199,9Ω | 0,1Ω | ±(4% m.v. + 3 Digits) |
200...1999Ω | 1Ω |
Measurement of short circuit loop impedance ZL-PE RCD (without RCD tripping)
Measuring range according to IEC61557: 0,43...1999? for 1,2m test leads; 0,50...1999? for UNI-SCHUKO adapter
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(6% m.v. + 10 Digits) |
20,0...199,9Ω | 0,1Ω | ±(6% m.v. + 5 Digits) |
200...1999Ω | 1Ω |
Voltage measurement
Range | Resolution | Accuracy |
0,0...249,9V | 0,1V | ±(2% m.v. + 4 Digits) |
250...750V | 1V | ±(2% m.v. + 2 Digits) |
Electrical safety:
- type of insulation: double, according to IEC 61010-1
- measurement category: CAT IV 600V (CAT III 1000V)
- protection class acc. to EN 60529: IP54
Other technical data
- power supply: alkaline batteries or NiMH rechargeable batteries, LR14 (4 pcs)
- number of Z measurements (for alkaline batteries): > 5000
- time to Auto-OFF: 300 seconds
- data transmission: USB
- memory of measurement results: 990 cells, 3500 entries
- display: LCD segment
- dimensions: 288 x 223 x 75mm
- meter weight: ca. 2 kg
„m.v.” measured value